HVI's ventilation guidelines.
Ventilation products have differing capacities for moving air, making it important to ensure the product being selected has ample capacity for the application. HVI's Certified airflow rating appears on the product or on the HVI label displayed on each unit, in the manufacturer's literature describing the fan and in the HVI-Certified Products Directory.
The following guidelines will help you to determine the fan capacity required for your application.
HVI recommends the following intermittent ventilation rates for bathrooms:
Bathroom size | Calculation formula | Ventilation rate required |
Less than 100 square feet | 1 CFM per square foot of floor area | A minimum of 50 CFM |
More than 100 square feet | Add the CFM requirement for each fixture | Toilet 50 CFM Shower 50 CFM Bathtub 50 CFM Jetted tub 100 CFM |
Continuous ventilation at a minimum rate of 20 CFM may be used in lieu of an intermittent 50 CFM exhaust fan.
Recommended kitchen range hood ventilation rates vary greatly depending on the type of cooking performed and the location of the range. Kitchen range hoods mounted above the range capture contaminants with their canopy shapes and exhaust them effectively with relatively low air volume. Downdraft kitchen exhausters require a higher volume and velocity of air to adequately capture contaminants. They are an alternative when canopy style hoods are not desired due to location of the cooking surface and kitchen aesthetics; however, their performance cannot equal that of hoods that capture the rising column of air above the cooking surface. When considering a downdraft kitchen exhauster, consult the range manufacturer's recommendations.
Kitchen range hoods equipped with multiple speed settings allow low-level, quiet ventilation for light cooking with the ability for higher rates when needed.
Location of range | HVI-recommended ventilation rate per linear foot of range | Minimum ventilation rate per linear foot of range |
Against a wall | 100 CFM | 40 CFM |
In an island | 150 CFM | 50 CFM |
Width of hood against a wall | 2.5 feet (30 inches) | 3 feet (36 inches) | 4 feet (48 inches) |
HVI-recommended rate | 250 CFM | 300 CFM | 400 CFM |
Minimum | 100 CFM | 120 CFM | 160 CFM |
Note: Nonducted, recirculation kitchen range hoods provide no actual ventilation. For optimum kitchen air quality, always use kitchen range hoods, kitchen fans or downdraft kitchen exhausters that vent directly outside the home.
For continuous indoor air quality ventilation, a heat or energy recovery ventilator (HRV or ERV) should provide 0.35 air changes per hour. This calculation must consider the complete occupied volume of the house.
This rate can be more easily calculated by allowing 5 CFM per 100 square feet of floor area.
Total area of home (square feet) | Continuous ventilation rate |
1,000 square feet | 50 CFM |
2,000 square feet | 100 CFM |
3,000 square feet | 150 CFM |
In addition to this minimum, continuous ventilation rate, HRVs and ERVs often have additional capacity to provide higher ventilation rates to meet the occupants' needs. Such needs could occur as a result of larger gatherings of people; smoking; a hobby or activity using paint, glues or other air-quality contaminants; or for any other reason that requires additional ventilation to improve the quality of indoor air.
Local codes may require different continuous ventilation rates – always check with your building officials to determine the specific requirements for your area.
HVI recommends that a whole-house comfort ventilator have a minimum capacity to provide approximately one complete air change every two minutes within the occupied area. This flow rate will be great enough to create a perceptible "breeze" through the house. The required flow rate can be calculated by multiplying the gross square footage of the entire house (including unoccupied areas like closets) by 3. Be sure to include the "upstairs" area of multilevel homes. This formula assumes an eight-foot ceiling and takes into account typical unoccupied areas.
House area | Capacity in CFM |
1,000 square feet | 3,000 CFM |
2,000 square feet | 6,000 CFM |
3,000 square feet | 9,000 CFM |
A smaller fan can effectively cool the mass of the house, relying on other fans such as "paddle-fans" to create the breeze needed to cool the people. This lower flow rate can be determined by multiplying the square footage by 0.4.
2,000 square feet | 800 CFM |
3,000 square feet | 1,200 CFM |
For proper cooling and efficient operation, any whole-house comfort ventilator requires adequate, unobstructed outlets in the attic through soffit vents, grilles or louvers.
To calculate the amount of attic exhaust area you will need, divide the fan's capacity in CFM by 750.
Fan capacity | Exhaust area required |
1,000 CFM | 1.33 square feet |
4,800 CFM | 6.4 square feet |
NOTE: Large fans can put the house under significant negative pressure. At least one window should be open before the fan is operated.
Powered attic ventilators should provide at least 10 air changes per hour. Multiplying the total square footage of the attic by 0.7 will provide the rate required. For particularly dark or steep roofs, we recommend a slightly higher rating.
Attic area in square feet | CFM required | +15% for dark/steep roofs |
1,000 square feet | 700 CFM | 805 CFM |
2,000 square feet | 1,400 CFM | 1,610 CFM |
3,000 square feet | 2,100 CFM | 2,415 CFM |
The air being exhausted must be replaced by outside air drawn through vents under the eaves in the soffit. To calculate the total minimum soffit vent intake area in square inches, divide the CFM of the PAV by 300 and multiply the result by 144.
CFM of PAV | Soffit vent in net square inches |
805 CFM | 386 net square inches |
1,610 CFM | 773 net square inches |
2,415 CFM | 1,160 net square inches |
A minimum of one square foot of inlet area for every 300 CFM of HVI-Certified fan capacity is required for proper fan operation.
In all seasons, the attic space is warmer than the outside air. This results in a constant upward air movement due to the buoyancy of warmer air. This characteristic of air may be used to help create a flow of air ventilating the attic. Placing exhaust vents in the roof, the gables or at the ridge of the roof and providing adequate air intake vents in the soffits best accomplishes this. HVI recommends vent selection and placement such that 60 percent of the vent net free area is provided by intake vents placed at the under-eave area and 40 percent of the vent net free area is provided by exhaust vents on the roof, at the ridge or high in the gable area.
To determine the static ventilator net free area (NFA) needed for your attic space, determine the area of the attic in square feet. Divide that area by 150 to determine the square feet of attic ventilation needed. Since manufacturers of static ventilation products rate their products in square inches of NFA, it will be necessary to multiply that value by 144 to determine the square inches required.
Attic area in square feet | Ventilation area in square feet | Net free area in square inches |
1,000 square feet | 6.67 square feet | 960 square inches |
2,000 square feet | 13.3 square feet | 1,920 square inches |
3,000 square feet | 20.0 square feet | 2,880 square inches |
Static ventilation needs may be reduced if you have an uninterrupted ceiling vapor barrier installed with a rating of 0.1 perm or less. To calculate the ventilation required with such a vapor barrier, divide the square footage of the attic by 300 instead of 150.
Attic area in square feet | Ventilation area in square feet | Net free area in square inches |
1,000 square feet | 3.33 square feet | 480 square inches |
2,000 square feet | 6.67 square feet | 960 square inches |
3,000 square feet | 10.0 square feet | 1,440 square inches |
Use these numbers to select, proportion, and place static ventilation products.